The KL3201 and KL3202 analog input terminals allow resistance sensors to be connected directly. The Bus Terminal’s circuitry can operate the sensors using 2-wire or 3-wire connection techniques. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminals standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors in 3-wire connection. The run LEDs give an indication of the data exchange with the Bus Coupler. The error LEDs indicate sensor faults (e.g. a broken wire).
Technical data | KL3201 | KS3201 | KL3202 | KS3202 |
---|---|---|
Number of inputs | 1 | 2 |
Power supply | via the K-bus | |
Technology | 2-/3-wire | |
Sensor types | PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ) | |
Connection method | 2- or 3-wire (default: 3-wire) | |
Measuring range | -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors) | |
Resolution | 0.1 °C per digit | |
Conversion time | ~ 200 ms | ~ 250 ms |
Measuring current | typ. 0.5 mA | |
Measuring error | < ±1 °C | |
Electrical isolation | 500 V (K-bus/signal voltage) | |
Current consumption power contacts | – (no power contacts) | |
Current consumpt. K-bus | typ. 60 mA | |
Bit width in the process image | input: 1 x 16 bit data (1 x 8 bit control/status optional) | input: 2 x 16 bit data (2 x 8 bit control/status optional) |
Configuration | no address setting, configuration via Bus Coupler or controller | |
Special features | open-circuit recognition | |
Weight | approx. 70 g | |
Operating/storage temperature | 0…+55 °C/-25…+85 °C | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation | |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
Protect. class/installation pos. | IP 20/variable | |
Pluggable wiring | for all KSxxxx Bus Terminals | |
Approvals | CE, UL, Ex, GL |