¥ 2043.00
¥ 2043.00
¥ 2043.00
¥ 2089.00
¥ 2089.00
易卖工控网(www.ymgk.com)提供”086407-502 New spot supply of DC fiber optic panels for sale of imported products”,产品详情:品牌/厂家:ABB +8615359293870、型号:086407-502 +8615359293870、成色:全新、货期:现货 1天内发货、保修:180天,更多产品详情就上易卖工控网。
Basic information
Chinese name
Input/Output Module
alias
control module
effect
Receive feedback signals from devices
Functional effects
When a fire alarm occurs, the alarm controller activates the external control equipment that needs to be linked through the output module, such as smoke exhaust valves, air supply valves, fire resistant rolling shutter doors, fans, alarm bells, etc., and can accept the action response of the equipment.
The output module is connected to the loop bus of the controller and can be installed near the controlled equipment or inside the floor terminal module box. Electronic coding can be used for on-site coding. The output control logic of the output module can be programmed according to the engineering situation. After the controller receives the alarm signal from the detector, according to the pre programmed program, the controller transmits the linkage control signal to the output module through the bus, which starts the fire equipment that needs to be linked; After the device operates, it will receive a signal response.
characteristic
The input/output module is a bus based control interface that can be used to control dual action devices such as two-step fire resistant rolling shutter doors, water pumps, smoke exhaust fans, etc. Mainly used for position control of fireproof rolling shutter doors, it can control their position from upper to middle, as well as from middle to lower. At the same time, it can also confirm which position the fireproof rolling shutter door is in. This module can also be used as two independent input/output modules.
The input/output module has two consecutive encoding addresses, with a large encoding of 242. It can receive commands for two different actions from the controller and has the function of two different control outputs and confirming two different input response signals. The input signal required for this module is a normally open switch signal. Once the switch signal is activated, it is sent to the controller through the linkage bus. The linkage controller generates an alarm and displays the address number of the action device. When the module itself malfunctions, the controller will also generate an alarm and display the module number. This module has two pairs of normally open and normally closed contacts, as well as two sets of active outputs. The input and output have line detection functions.
The coding method of the module is electronic coding. After one coding address is assigned, the other coding address is automatically generated as: assigned address+1. This encoding method is simple and fast, and the electronic encoder produced by Gulf Company is used for on-site encoding.
Contact information: 15359213550
Contact person: He Gong
Email: geabbdcs@gmail.com 386353502@qq.com
Official website: https://www.gyamazon.com , http://www.geabb.com
Main technical indicators
(1) Working voltage:
Bus voltage: Bus 24V
Power supply voltage: DC24V
(2) Monitoring current:
Bus current ≤ 1mA
Power supply current ≤ 6mA
(3) Action current: Bus current ≤ 4mA
Power supply current ≤ 35mA
(4) Wire system: connected to the controller using a non polarity signal two bus, and connected to the DC24V power supply using a non polarity power two bus
(5) Output capacity: DC24V/1A (the sum of two sets of output capacities is DC24V/1A)
(6) Output control method: pulse and level (relay normally open/normally closed passive contact output, relay closing time is 10s when pulse is activated)
(7) Factory setting: Two normally open inspection lines
(8) Usage environment:
Temperature: -10 ℃~+55 ℃
Relative humidity ≤ 95%, no condensation
(9) Shell protection level: IP30
(10) Overall dimensions:
110mm × 86mm × 43mm (with bottom shell)