当控制站全部断电后,监控画面上两个系统报警红灯亮,通讯中断,数据全部不刷新,所有自调系统完全失控,调节阀将恢复到初始状态,气开阀全关,气关阀全开。此时,应立即紧急处理或停车,同时到现场进行操作。
5、注意所有操作站全部断电的情况
此时,查看控制站电源指示灯是否正常,卡件诊断指示灯有无故障红灯,绿灯表示卡件正常工作,若以上都正常,则可以确定控制站工作正常,自调系统工作正常,只是操作工暂时看不到监控画面,且不能对现场进行遥控操作,立即通知微机维修人员进行维修,并到现场进行监控。
6、调节阀仪表气源压力低或仪表空气全部断气
当发现多个自调系统失灵,监控画面上自调阀阀位在全开或全关位置,立即检查仪表气源压力,若气源压力小于0.4MPa,则不正常,检查气源管道有无堵塞或漏气现象;若气源压力小于0.2MPa,立即进行紧急停车。将监控画面上的自调系统全部打到手动,将调节阀阀位调到安全位置,通知仪表工检查气源,同时到现场进行操作,关闭调节阀两端的截止阀,用旁路阀操作。DEIF Delomatic 3 CM-2 1044220190G自动化设备 DEIF Delomatic 3 CM-2 1044220190G自动化设备 DEIF Delomatic 3 CM-2 1044220190G自动化设备 When the control station is completely powered off, the red alarm light of the two systems on the monitoring screen is on, the communication is interrupted, the data is not refreshed, all self-regulation systems are completely out of control, the regulating valve will return to the initial state, the gas opening valve will be fully closed, and the gas closing valve will be fully opened. At this time, emergency treatment or shutdown shall be carried out immediately, and operation shall be carried out on site at the same time.
5. Pay attention to the power failure of all operation stations
At this time, check whether the power indicator of the control station is normal and whether the card diagnosis indicator is faulty. The red light and the green light indicate that the card is working normally. If all the above are normal, it can be determined that the control station is working normally and the automatic adjustment system is working normally, but the operator can't see the monitoring picture temporarily and can't remotely operate the site. Immediately notify the microcomputer maintenance personnel to repair and monitor the site.
6. The pressure of instrument air source of regulating valve is low or all instrument air is cut off
When multiple self regulating systems are found to be out of order and the self regulating valve on the monitoring screen is in the fully open or fully closed position, immediately check the instrument air supply pressure. If the air supply pressure is less than 0.4MPa, it is abnormal. Check whether the air supply pipeline is blocked or leaking; If the air source pressure is less than 0.2MPa, conduct emergency shutdown immediately. Turn all the self-adjusting systems on the monitoring screen to manual, adjust the valve position of the regulating valve to the safe position, notify the instrument worker to check the air source, and operate on site at the same time, close the stop valves at both ends of the regulating valve and operate with the bypass valve.


易卖工控网供应商瑞昌明盛自动化为您提供DEIF Delomatic 3 CM-2 1044220190G自动化设备的详细产品价格、产品图片等产品介绍信息,您可以直接联系商家获取DEIF Delomatic 3 CM-2 1044220190G自动化设备的具体资料,联系时请说明是在易卖工控网看到的。

安全提示:
请勿随意接收任何来源不明的文件,请勿随意点击任何来源不明的链接。涉及资金往来的事项请务必仔细核对资金往来信息。
内容声明:
易卖工控为第三方交易平台及互联网信息服务提供者,易卖工控所展示的商品/服务的标题、价格、详情等信息内容系由店铺经营者发布,其真实性、准确性和合法性均由店铺经营者负责。易卖提醒用户购买商品/服务前注意谨慎核实。如用户对商品/服务的标题、价格、详情等任何信息有任何疑问的,请在购买前与店铺经营者沟通确认;易卖工控存在海量店铺,如用户发现店铺内有任何违法/侵权信息,请立即向易卖工控举报并提供有效线索。

0

购物车

客服

收藏

公众号

公众号

反馈

︿

顶部

询价成功
发布询价成功
请保持通信畅通,以便卖家及时与您联系
点击这里给我发消息 点击这里给我发消息